Free MemberNot Verified

Guangzhou Hiseer Air Conditioning Co.,Ltd

HISEER, the brand name itself means high seasonal energy efficiency ratio. Impressed by the founder’s specialist knowledge and experience at refrigeration fields, helped by the closed cooperation with engineers from wo ...

Guangzhou Hiseer Air Conditioning Co.,Ltd
Xicheng Industry Zone, Renhe Town, Baiyun District
Guangzhou, GU 510000
China

Manufacturer

Product Categories

Modular ground source electric heat pump efficiency

Modular ground source electric heat pump efficiency
Category:
Price:
Contact Supplier for pricing
Brand:
HISEER
Model:
GSWW60-DNNNE
Delivery Lead Time:
15-20 days after receiving payment
Packaging:
plywood
Payment Terms:
  • L/C

Product Description

Detail: Modular ground source electric heat pump efficiency

GSWW60-DNNNE, HISEER modular geothermal ground source heat pump, can be easily connected together for any size heating &

cooling system at the project spot. Maximum 64 units can be worked together for the largest 3840KW output capacity.

Geothermal ground source heat pump is a electrically powered system that takes advantage of the earths constant ground temperature to provide heating, cooling and hot water for your home or business.

Water to water system pumps heat through the use of a simple refrigeration system, it pumps heat from the warm earth in the winter and move it into your house or business. In the summer, the process is reversed. Since it costs far less to move heat than to make it, much less energy is consumed.

For closed loop system, water or an antifreeze solution is circulated through plastic pipes buried beneath the earths surface. During the winter the fluid collects heat from the earth and carries it through the system and placing it in the ground.

Open systems operate on the same principle as closed loop systems and can be installed where an adequate supply of suitable water is available and open discharges is feasible.

Loops can be installed three ways: horizontally, vertically or in a pond or lake. The type chosen depends on the available land area and the soil and rock type at the installation site.

GSWW60-DNNNE technical data

- - - -
ModularGeothermalHeatPump(heatingonly) |
Heatpump | Type | GSWW60-DNNNE |
Dimensions, weights, connectiondimensions |
Dimensions | HxWxD | 1620x550X1250 |
Weight | kg | 420 |
Refrigerant | Type | R407C |
Fillingweight | kg | 10 |
Permissibleoperatingpressure | Mpa | 3 |
Pipeconnector-hotside | Inch | G4 |
Pipeconnector-coldside | Inch | G4 |
Evaporator | Type | Brazedplateheatexchanger |
Condenser | Type | Brazedplateheatexchanger |
Compressor | | 2xScroll |
PerformanceHeatpump |
Heatoutput | atB0/W35(1) | kW | 60 |
Powerconsumption | kW | 14.6 |
Performancefactor | | 4.11 |
Hotsidevolumeflow(3) | m3/h | 10.4 |
Coldsidevolumeflow(4) | m3/h | 10.2 |
Heatoutput | atW10/W35(2) | kW | 77 |
Powerconsumption | kW | 14.9 |
Performancefactor | | 5.17 |
Hotsidevolumeflow | m3/h | 13.4 |
Coldsidevolumeflow | m3/h | 13.6 |
Processmedium | | Brinemadefromwaterwith33Vol.%ethyleneglycol |
Power | Type | Triplephase |
Soundpowerlevel | dB(A) | 52 |
(1)B0/W35=Brinewaterinlettemperature0, heatingflow35 |
(2)W10/W35=Wellwaterinlettemperature10, heatingflow35 |
(3)Heatingflowfor5Ktemperaturespan | | |
(4)Heatsourceflowfor4Ktemperaturespan | |
- - - -